AS-i 3.0 Command Interface Command Interface Examples
Subject to reasonable modifications due to technical advances Id.-No.: 102875 Issue date - 3.12.2007 EUCHNER GmbH + Co. KG
Kohlhammerstraße 16, D-70771 Leinfelden-Echterdingen Tel. +49/711/7597-0, Fax +49/711/753316
82
No result because toggle bit = 0.
Set the toggle bit:
Request: SET_PCD
Byte 1 25
hex
(SET_PCD)
Byte 2 00
hex
(T = 0, master 1, single master)
Byte 3 04
hex
(slave address to write to master)
Byte 4 EF
hex
(ID + IO to configurate)
Byte 5 37
hex
(xID2 + xID1 to configurate)
Byte 6 00
hex
……
Byte 12 00
hex
Response
Byte 1 00
hex
(or old values)
Byte 2 00
hex
(or old values)
Byte 3 00
hex
(or old values)
Byte 4 00
hex
(or old values)
……
Byte 12 00
hex
(or old values)
Request: SET_PCD
Byte 1 0C
hex
(SET_PCD)
Byte 2 80
hex
(T = 1, master 1, single master)
Byte 3 04
hex
(slave address to write to master)
Byte 4 EF
hex
(ID + IO to configurate)
Byte 5 37
hex
(ID + IO to configurate)
Byte 6 00
hex
……
Byte 12 00
hex
Response
Byte 1 25
hex
Byte 2 80
hex
(T = 1, result = 0)
Byte 3 00
hex
(or old values)
Byte 4 00
hex
(or old values)
……
Byte 12 00
hex
(or old values)