Euchner AS-i 3.0 Command Interface Instrukcja Użytkownika Strona 84

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 98
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 83
AS-i 3.0 Command Interface Command Interface Examples
Subject to reasonable modifications due to technical advances Id.-No.: 102875 Issue date - 3.12.2007 EUCHNER GmbH + Co. KG
Kohlhammerstraße 16, D-70771 Leinfelden-Echterdingen Tel. +49/711/7597-0, Fax +49/711/753316
84
Setting the toggle bit:
The new list of protected slaves (LPS) is written.
4. Write permanent parameter (power on parameter) to master
Example as above: 16 bit module at address 4 with PP = 07
hex
No result because toggle bit = 0
Request: SET_LPS
Byte 1 29
hex
Byte 2 80
hex
(T = 1, master 1, single master)
Byte 3 00
hex
Byte 4 10
hex
(LDS byte 0)
Byte 5 00
hex
(LDS byte 1)
……
Byte 11 00
hex
(LDS byte 7)
Byte 12 00
hex
Response
Byte 1 29
hex
Byte 2 80
hex
(T = 1, result = 0)
Byte 3 00
hex
(or old values)
……
Byte 12 00
hex
(or old values)
Request: SET_PP
Byte 1 43
hex
(SET_PP)
Byte 2 00
hex
(T = 0, master 1, single master)
Byte 3 04
hex
(slave address to write to master)
Byte 4 07
hex
(PP to write (use low nibble))
Byte 5 00
hex
(LDS byte 1)
……
Byte 12 00
hex
Response
Byte 1 00
hex
(or old values)
Byte 2 00
hex
(or old values)
……
Byte 12 00
hex
(or old values)
Przeglądanie stron 83
1 2 ... 79 80 81 82 83 84 85 86 87 88 89 ... 97 98

Komentarze do niniejszej Instrukcji

Brak uwag