AS-i 3.0 Command Interface Command Interface Examples
Subject to reasonable modifications due to technical advances Id.-No.: 102875 Issue date - 3.12.2007 EUCHNER GmbH + Co. KG
Kohlhammerstraße 16, D-70771 Leinfelden-Echterdingen Tel. +49/711/7597-0, Fax +49/711/753316
85
Setting the toggle bit:
The permanent parameter for the 16 bit module is written.
This command must be repeated for all 31 A-slaves and all 31 B-slaves. If you
don't connect a slave to an address, write the default value to the master (F
hex
) as
a permanent parameter.
5. Switch Master to Protected Mode
No result because toggle bit = 0.
Request: SET_PP
Byte 1 43
hex
(SET_PP)
Byte 2 80
hex
(T = 0, master 1, single master)
Byte 3 04
hex
(slave address to write to master)
Byte 4 07
hex
(PP to write (use low nibble)
Byte 5 00
hex
……
Byte 12 00
hex
Response
Byte 1 43
hex
Byte 2 80
hex
(T = 1, Result = 0)
Byte 3 00
hex
……
Byte 12 00
hex
Request: SET_OP_MODE
Byte 1 0C
hex
(SET_OP_MODE)
Byte 2 00
hex
(T = 0, master 1, single master)
Byte 3 00
hex
(= protected mode)
Byte 4 00
hex
……
Byte 12 00
hex
Response
Byte 1 00
hex
(or old values)
Byte 2 00
hex
(or old values)
……
Byte 12 00
hex
(or old values)